For data center air conditioning systems (especially precision air conditioners or CRAC units), the vacuum level requirement mainly depends on whether the system has a compressor (with refrigerant) and the manufacturer’s specifications. Here are the industry-standard guidelines:
✅ General Standard
-
Target vacuum level:
500 microns or lower (≈0.66 mbar, ≈66 Pa)
This is the common HVAC and data center standard to ensure the system is almost free of moisture and air. -
High Standard / Best Practice:
300 microns or lower
Recommended for large refrigeration systems or those sensitive to moisture (e.g., low-temperature systems, long piping).
✅ Why 500 microns?
-
A refrigeration system must be free of moisture and air; otherwise, it can cause:
-
Freeze-up (ice blockages)
-
Acid formation leading to compressor damage
-
Reduced heat transfer efficiency
-
-
Below 500 microns means the system pressure is close to a true vacuum, and most residual moisture has been removed.
✅ Vacuum Procedure Recommendation
-
Pull down to about 1500 microns first, hold for a few minutes to check for leaks.
-
Then pull down to 500 microns or lower, and hold for 10–15 minutes without rising.
-
If the pressure rises quickly after stopping the pump, there’s likely a leak or residual moisture.
在数据中心空调(尤其是精密空调或CRAC系统)安装和维护过程中,抽真空的标准主要取决于系统中是否有压缩机(带制冷剂)以及厂商规范。以下是行业通用标准:
✅ 常规标准
-
目标真空度:
500 micron 或更低(≈0.66 mbar,≈66 Pa)
这是绝大多数 HVAC 和数据中心空调行业的通用标准,确保系统内部接近无水分和无空气。 -
高标准/最佳实践:
300 micron 或更低
用于大型制冷系统或对湿气敏感的系统(如低温系统、长管路系统)。 -
✅ 为什么是 500 micron?
-
制冷剂系统必须确保内部没有水分和空气,否则会导致:
-
冻结堵塞(冰堵)
-
酸性物质腐蚀压缩机
-
降低换热效率
-
-
500 micron 以下表示系统压力已经非常接近真空状态,残余水分基本被蒸发带走。
-
✅ 抽真空步骤建议
-
先抽到 1500 micron,保持几分钟,确认泄漏。
-
再抽到 500 micron 或更低,并保持 10~15 分钟稳定(不回升)。
-
如果停泵后上升速度快,说明有泄漏或水分未完全去除。